8500 -10500 kW Output

The PO Series burner can operate on oil (Class D light oil, Class G HFO) and is available in standard outputs from 3.3MW to 18MW. The PO Series burner is commonly used on large industrial steam and hot water boilers.

Information

Key Features:

  • Available in monoblock design up to P310 or a duoblock design with a floor mounted combustion air fan
  • Low NOx Head
  • Electronic micro modulation air fuel ratio control with individual valve servo motors as standard
  • Variable Speed Drive (VSD) combustion air fan motor
  • Air inlet silencer (< 85dBA)
  • Oxygen trim for improved efficiency and reduced emissions
  • Separate or integrated water level controls for steam boilers
  • Data Transfer Interface for BMS control

All P series burners are design and manufactured in accordance with EN267 and EN676.

Technical Data

ModelPO

490/12.1

490/12.5

490/12.8

490/13.2

490/13.6

490/13.9

490/14.3

Output (nett CV)

MW

10.9

11.2

11.5

11.9

12.2

12.5

12.9

Fan Size

kW

30

30

30

30

30

30

30

Pump Motor

(Distillate Fuel)

kW

5.5

5.5

5.5

5.5

5.5

5.5

5.5

Pump Motor

(Residual Fuel)

kW

5.5

5.5

5.5

5.5

5.5

5.5

5.5

Pre-heater

(Residual Fuel only)

kW

54

54

54

54

54

54

54

Electrical Supply

V/Hz

400/50

400/50

400/50

400/50

400/50

400/50

400/50

Oil inlet pressure

psi

5 to 10

5 to 10

5 to 10

5 to 10

5 to 10

5 to 10

5 to 10

Fuel pump

T5

T5

T5

T5

T5

T5

T5

Operation

Fully Modulating

Fully Modulating

Fully Modulating

Fully Modulating

Fully Modulating

Fully Modulating

Fully Modulating

Control Unit

Autoflame

Mini Mk7

Autoflame

Mini Mk7

Autoflame

Mini Mk7

Autoflame

Mini Mk7

Autoflame
Mini Mk7

Autoflame
Mini Mk7

Autoflame
Mini Mk7

Turndown

up to 4:1

up to 4:1

up to 4:1

up to 4:1

up to 4:1

up to 4:1

up to 4:1

Flame Monitor

UV Sensor

UV Sensor

UV Sensor

UV Sensor

UV Sensor

UV Sensor

UV Sensor

Flame tube lengths

mm

430/610

430/610

430/610

430/610

430/610

430/610

430/610

Noise

dBA

96

96

96

96

96

96

96

NOx

mg/kWh

200-280

200-280

200-280

200-280

200-280

200-280

200-280

CO

mg/kWh

<110

<110

<110

<110

<110

<110

<110