3453 -4129 kW Output

All N series burners are custom-built and designed for easy maintenance. This range is typically suited for high resistance, hot water and steam boilers. This burner series can fire on Class C to G oil and is designed for 2 stage High/Low or fully modulating operation. NOG burners are accompanied with a burner mounting pumping and heating unit to heat the Class G oil for atomisation. The oil temperature is maintained to allow the burner an immediate restart reducing downtime.

Information

Key Features:

  • Quick and easy installation
  • Reliable and trouble free operation
  • Industry standard components available
  • Most components can be easily accessed allowing for easy maintenance.
  • Burner mounted control panel available for heavy oil range.

All N Series burners have been design in accordance with EN676 and EN267.

Technical Data

Type

NOL150

Capacity

kW

3453 - 4129

Fan Motor

V/ph/Hz

380-420 / 3 / 50

150-36

150-41

150-44

kW

7.5

11

15

Start current

A/each phase

57

72

92

Run current

A/each phase

15.6

22.8

29.7

Cable size

mm2

4

6

10

Fuse

HRC (A)

25

30

40

Control unit

LAL

Fuel pump

HP Technik

Oil Pump Motor

kW

0.75

Fuel connection

inch BSP

0.75

Control Options

2 Stage / Modulating

Noise @ 1m

dBA

91

91

92

Gross weight

kg

370

Volume

m3

1.872