2083 -3293kW Output
This burner is suitable for use on natural gas and LPG (Towns gas and biogas on request) with-
- two stage high/low
- or modulating operation.
All N series burners are custom-built and designed for easy maintenance. This range is typically suited for high resistance, hot water and steam boilers.
Information
Key Features:
- Quick and easy installation
- Reliable and trouble free operation
- Industry standard components available
- Most components can be easily accessed allowing for easy maintenance.
Also available:
- Larger gas trains
- Electronic Micro Modulating control
- Variable speed drive to reduce power consumption and noise levels.
All N series burners have been design in accordance with EN676 and EN267.
Information
Type | NG125 | ||
Capacity | kW | 2120-2751 | |
Fan Motor | V/ph/Hz | 380-420/3/50 | |
125-36 | 125-41 | ||
Motor | kW | 7.5 | 11 |
Start Current | A/each phase | 57 | 72 |
Run Current | A/each phase | 15.6 | 22.8 |
Cable size | mm2 | 4 | 6 |
Fuse | HRC (A) | 25 | 30 |
Control unit | LFL | ||
Operation Options | 2 Stage / Mod | ||
Flame monitoring | UV Cell | ||
Air damper motor | • | ||
Max inlet gas pressure | mbar | 300 | |
Noise @ 1m | dBA | 92 | 94 |
Gross weight | kg | 330 | |
Volume | m3 | 2.344 |