225 -860kW Output

These burners are available for use on natural gas, LPG, towns gas and biogas with-

  • single stage on/off
  • two stage high/low
  • or modulating operation.

They are typically suited for commercial hot water boiler systems and steam boiler systems.

Information

Key Features:

  • Quick and easy installation
  • Reliable and trouble free operation
  • Industry standard components available
  • Most components can be easily accessed allowing for easy maintenance.

Also available:

  • Quick and easy installation
  • Larger gas train options
  • Speed control (available only on certain models) to improve fuel efficiency and energy saving.

All M series burners have been design in accordance with EN676 and EN267.

Technical Data

Type

MGN860-LN

Capacity

kW

225-860

Motor

V/Hz

kW/A (Fuse) + Control fuse

400 / 50

1.1 / 3 x 16 + 1 x 10.0

Start / Run Current

Amps

6.5 / 3.6

Control box

DMG 972 / MPA 22

Flame monitoring

Ionisation

Operation mode

2 stage or modulating

Gross weight-burner

kg

45

Gross weight-standard gas train

kg

12

Noise emission

dBA

≤ 78

NOx emission

mg/kWh

< 80