1579 -2120kW Output
This burner is suitable for use on natural gas and LPG (Towns gas and biogas on request) with-
- two stage high/low
- or modulating operation.
All N series burners are custom-built and designed for easy maintenance. This range is typically suited for high resistance, hot water and steam boilers.
Information
Key Features:
- Quick and easy installation
- Reliable and trouble free operation
- Industry standard components available
- Most components can be easily accessed allowing for easy maintenance.
Also available:
- Larger gas trains
- Electronic Micro Modulating control
- Variable speed drive to reduce power consumption and noise levels.
All N series burners have been design in accordance with EN676 and EN267.
Information
Type | NG80 | |
Capacity | kW | 1579-2120 |
Motor | V/ph/Hz kW | 380-420/3/50 5.5 |
Start Current | A/each phase | 40 |
Run Current | A/each phase | 11.3 |
Cable size | mm2 | 2.5 |
Fuse | HRC (A) | 20 |
Control unit | LFL | |
Operation Options | 2 Stage / Mod | |
Flame monitoring | UV Cell | |
Air damper motor | • | |
Max inlet gas pressure | mbar | 300 |
Noise @ 1m | dBA | 91 |
Gross weight | kg | 170 |
Volume | m3 | 1.23 |