8500 -10500 kW Output
The PO Series burner can operate on oil (Class D light oil, Class G HFO) and is available in standard outputs from 3.3MW to 18MW. The PO Series burner is commonly used on large industrial steam and hot water boilers.
Information
Key Features:
- Available in monoblock design up to P310 or a duoblock design with a floor mounted combustion air fan
- Low NOx Head
- Electronic micro modulation air fuel ratio control with individual valve servo motors as standard
- Variable Speed Drive (VSD) combustion air fan motor
- Air inlet silencer (< 85dBA)
- Oxygen trim for improved efficiency and reduced emissions
- Separate or integrated water level controls for steam boilers
- Data Transfer Interface for BMS control
All P series burners are design and manufactured in accordance with EN267 and EN676.
Technical Data
ModelPO | 490/12.1 | 490/12.5 | 490/12.8 | 490/13.2 | 490/13.6 | 490/13.9 | 490/14.3 | |
Output (nett CV) | MW | 10.9 | 11.2 | 11.5 | 11.9 | 12.2 | 12.5 | 12.9 |
Fan Size | kW | 30 | 30 | 30 | 30 | 30 | 30 | 30 |
Pump Motor (Distillate Fuel) | kW | 5.5 | 5.5 | 5.5 | 5.5 | 5.5 | 5.5 | 5.5 |
Pump Motor (Residual Fuel) | kW | 5.5 | 5.5 | 5.5 | 5.5 | 5.5 | 5.5 | 5.5 |
Pre-heater (Residual Fuel only) | kW | 54 | 54 | 54 | 54 | 54 | 54 | 54 |
Electrical Supply | V/Hz | 400/50 | 400/50 | 400/50 | 400/50 | 400/50 | 400/50 | 400/50 |
Oil inlet pressure | psi | 5 to 10 | 5 to 10 | 5 to 10 | 5 to 10 | 5 to 10 | 5 to 10 | 5 to 10 |
Fuel pump | T5 | T5 | T5 | T5 | T5 | T5 | T5 | |
Operation | Fully Modulating | Fully Modulating | Fully Modulating | Fully Modulating | Fully Modulating | Fully Modulating | Fully Modulating | |
Control Unit | Autoflame Mini Mk7 | Autoflame Mini Mk7 | Autoflame Mini Mk7 | Autoflame Mini Mk7 | Autoflame | Autoflame | Autoflame | |
Turndown | up to 4:1 | up to 4:1 | up to 4:1 | up to 4:1 | up to 4:1 | up to 4:1 | up to 4:1 | |
Flame Monitor | UV Sensor | UV Sensor | UV Sensor | UV Sensor | UV Sensor | UV Sensor | UV Sensor | |
Flame tube lengths | mm | 430/610 | 430/610 | 430/610 | 430/610 | 430/610 | 430/610 | 430/610 |
Noise | dBA | 96 | 96 | 96 | 96 | 96 | 96 | 96 |
NOx | mg/kWh | 200-280 | 200-280 | 200-280 | 200-280 | 200-280 | 200-280 | 200-280 |
CO | mg/kWh | <110 | <110 | <110 | <110 | <110 | <110 | <110 |